Analysis of failures and abnormal situations during the commissioning
Codes of abnormal situations

The abnormal situations codes used in the abnormal situations Archive, and the meanings of parameter associated with the appearance of this code

№ bo

Codes

Meanings of codes

1

The measured unconverted flowrate is less than the lower limit of unconverted range of the meter

Measured value of unconverted flowrate

2

The measured unconverted flowrate is greater than the upper limit of unconverted range of the meter

Measured value of unconverted flowrate

3

The value of unconverted flowrate is equal to 0 (the number of incoming pulses from the gas meter to the corrector is less than one for 1 hour)

The substitutional value of unconverted flowrate, equal to 0

4

Failure of pressure measuring channel

The substitutional value of pressure for the upper limit of the measurement range

5

The measured pressure is less than the lower limit of unconverted measurement range

Measured pressure value

6

The measured pressure is greater than the upper limit of unconverted measurement range

Measured pressure value

7

Gas temperature measuring channel failure

The substitutional value of the gas temperature

8

The measured gas temperature is less than the lower limit of unconverted measurement range

Measured value of gas temperature

9

The measured gas temperature is greater than the upper limit of unconverted measurement range

Measured value of gas temperature

10

The actuation of "watchdog" reed switch

The substitutional value of unconverted or converted flowrate

11

12

13

Failure in operation of electronics

 

14

Differential pressure channel failure or lack of differential pressure transducer

Measurement is not being performed ("zero")

15

The measured differential pressure is less than the lower limit of unconverted measurement range

Measured value of pressure drop

16

The measured differential pressure is greater than the upper limit of unconverted measurement range

Measured value of pressure drop

17

Failure of the ambient temperature measuring channel or absence of a temperature transducer

Measurement is not being performed ("zero")

18

The measured ambient temperature is less than the lower limit of unconverted measurement range

Measured value of ambient temperature

19

The measured ambient temperature is greater than the upper limit of unconverted measurement range

Measured value of ambient temperature